Product Model

OT250E04WP

In Stock
Last updated: 2025/4/19
ABB OT250E04WP

Selling Points

  • 1IP65 Protected Handle: The handle is IP65 protected, ensuring durability in harsh environments.
  • 2Wide Phase Distance: The phase barriers are mounted as standard, providing a wide distance between phases for enhanced safety.
  • 3Padlockable Handle: The handle is padlockable in the off-position and interlocked in the on-position for secure operation.
  • 4High Insulation Voltage: Rated insulation voltage (Ui) is 1000 V, ensuring reliable electrical insulation.
  • 5Compact Dimensions: The product measures 181 mm in width, 150 mm in height, and 83 mm in depth, making it space-efficient.
Product Details
OT250E04WP
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301265D0201
Pollution Degree
3
Product Net Width
212.5 mm
Product Net Height
170 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.1 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
Front IP00
Distance Between Phases
Wide phase distance
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
(315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 75 kW (400 ... 415 V) 145 kW (500 V) 170 kW (690 V) 250 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
Wide phase distance
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 04 (Left Side)
Terminal Type
Lug terminals
Terminal Width
20 mm
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661330
E-Number (Norway)
4337885
E-Number (Sweden)
3171191
Manufacturer ID
1SCA022744R3810

Specifications may be subject to change without notice