Product Model

OT250ES30

In Stock
Last updated: 2025/4/26
ABB OT250ES30

Selling Points

  • 1High-Voltage Capability: Rated for 1000 V main circuit voltage and 12 kV impulse withstand voltage.
  • 2Robust Construction: Made with rigid acid-proof steel for durability and reliability.
  • 3Efficient Operation: Handles 250 A operational current at various voltage levels (380-415 V, 500 V, 690 V).
  • 4IP00 Protection: Front IP00 degree of protection for safe operation in harsh environments.
  • 5Technical Support: Backed by Proax's highly trained technical team for seamless integration and support.
Product Details
OT250ES30
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301265D0201
Pollution Degree
3
Product Net Width
181.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82 mm
Product Net Weight
1.5 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Side operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 75 kW (400 ... 415 V) 145 kW (500 V) 170 kW (690 V) 250 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 30 (Right Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5293 >> Switch disconnector
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA022869R9900

Specifications may be subject to change without notice