Product Model

OT250ESUR3TZ

In Stock
Last updated: 2025/4/23
ABB OT250ESUR3TZ

Selling Points

  • 1High-Performance Operation: Designed for reliable performance in extreme conditions.
  • 2Robust Safety Features: Meets IEC/EN 60664-1 standards with a rated insulation voltage of 1000 V.
  • 3Compact Design: Compact dimensions (181.5 mm width, 150 mm height, 82 mm depth) for space-efficient installations.
  • 4Flexible Installation: Base mounting type with lug terminals, suitable for various electrical configurations.
  • 5Enhanced Durability: Constructed with a steel sheet enclosure and IP65 rating for durability and protection.
Product Details
OT250ESUR3TZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
31.75 kg
Cable Entry Position
Bottom/Bottom
Cable Outlets Per Side
Blank / 4xring-flange+ø25.5mm
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Stainless steel
Handle Color
Stainless Steel
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Special Functions
EMC
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 22 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642116
E-Number (Sweden)
3135029
Manufacturer ID
1SCA102320R1001

Specifications may be subject to change without notice