Selling Points
- 1High EMC safety for reliable operation in harsh environments.
- 2Robust stainless steel enclosure for durability and resistance to corrosion.
- 3IP65 protection ensures dust and water resistance.
- 4Mounted auxiliary contact with 2NO1NC configuration for added functionality.
- 5Designed for 415V AC23, 250A, 132kW operational power.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
Product Net Width | 400 mm | Product Net Height | 800 mm |
Product Net Depth / Length | 230 mm | Product Net Weight | 25.55 kg |
Cable Entry Position | Bottom/Bottom | Cable Outlets Per Side | Blank / Knock-outs: 2x63.5mm, 2x50.5mm, 2x40.5mm, 25.5mm, 20.5mm |
Connecting Capacity Main Circuit | Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm² | Conventional Thermal Current (Ithe) | Fully Enclosed 250 A |
Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
Enclosure Type | MSC | Handle Color | Black |
Handle Type | Pistol handle | Impact Resistance Rating | Housing IK09 |
Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC | Mechanical Durability | 20000 |
Mounted Auxiliary Contacts | 2 NO, 1 NC | Neutral Type | No neutral terminal |
Number of Auxiliary Contacts NC | 1 | Number of Auxiliary Contacts NO | 2 |
Number of Poles | 3P | Pollution Degree | 3 |
Position of Line Terminals | Bottom In - Bottom Out | Power Loss | at Rated Operating Conditions per Pole 6.5 W |
Rated Conditional Short-Circuit Current (Inc) | 40.5 kA | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A |
Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW | Rated Operational Voltage | Main Circuit 1000 V |
Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 30 kA (690 V AC) 1000Vac kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 8 kA |
Recommended Screw Driver | Main Circuit M8 | Standards | IEC 60947-1, -3 |
Switches Operating Mechanism | On the Front of the Switch | Terminal Type | Bolt |
Tightening Torque | Main Circuit 22 N·m | Recommended Screw Driver | Main Circuit M8 |
Tightening Torque | Main Circuit 22 N·m | Object Classification Code | Q |
ETIM 8 | EC000216 - Switch disconnector | ETIM 9 | EC000216 - Switch disconnector (low voltage) |
UNSPSC | 39122205 | IDEA Granular Category Code (IGCC) | 5166 >> Safety switch |
eClass | V11.1 : 27371403 | WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
Manufacturer ID | 1SCA161666R1001 |
Specifications may be subject to change without notice