Selling Points

  • 1Rigid Glass Reinforced Polycarbonate Enclosure: Durable and UV-protected for long-lasting performance.
  • 2IP65 Rating: Protected against low-pressure water jets, suitable for both outdoor and indoor applications.
  • 3Padlockable Handle: Secure with three padlocks for added safety.
  • 4Interlocked Cover: Ensures safe operation by preventing accidental cover opening.
  • 5PE Terminals Included: Easy cable connections with included PE terminals.
Product Details
OT250KGCC3T
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
380 mm
Product Net Height
560 mm
Product Net Depth / Length
180 mm
Product Net Weight
7.366 kg
Cable Entry Position
Bottom/Bottom
Cable Outlets Per Side
II-flange / II-flange
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 2pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Bottom In - Bottom Out
Position of PE Terminals
Bottom In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 22 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642408
E-Number (Norway)
1429338
Manufacturer ID
1SCA022276R9640