Product Model

OT250KLCC6AZ

In Stock
Last updated: 2025/4/25
ABB OT250KLCC6AZ

Selling Points

  • 1Designed to withstand harsh environments with an IP65 rating.
  • 2Built with high-quality materials for long-lasting performance.
  • 3Handles high thermal currents, ensuring reliable operation under demanding conditions.
  • 4Features knock-out openings and cable entries from the bottom for straightforward installation.
  • 5Includes padlockable handles, cover interlocks, and gas pressure relief for enhanced safety.
Product Details
OT250KLCC6AZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
41.14 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
4xC-flange / 4xC-flange, Knock-outs: 2x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 8pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
4 NO, 2 NC
Mounted Auxiliary Contacts
4 NO, 2 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
2
Number of Auxiliary Contacts NO
4
Number of Poles
6P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 22 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022512R8380

Specifications may be subject to change without notice