Product Model

OT250KLUU3BZ

In Stock
Last updated: 2025/4/19
ABB OT250KLUU3BZ

Selling Points

  • 1UV Protection and Ingress Protection: Designed to withstand UV light and low-pressure water jets, ensuring durability in harsh outdoor environments.
  • 2Galvanized Steel Enclosure: Constructed with a galvanized steel enclosure and polyester coating for enhanced durability and protection.
  • 3Gas Pressure Relief Function: Equipped with an inbuilt gas pressure relief function to protect users from internal arcs.
  • 4Padlockable Handle and Interlock Function: Features a padlockable handle and interlock function for secure operation and maintenance.
  • 5Comprehensive Warranty: Backed by a 3-year warranty for peace of mind and reliable performance.
Product Details
OT250KLUU3BZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
600 mm
Product Net Depth / Length
230 mm
Product Net Weight
15.81 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
Blank /Blank
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
0 NO, 0 NC
Neutral Type
Detachable neutral
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Poles
3
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 22 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022602R0710

Specifications may be subject to change without notice