Product Model

OT25M4

In Stock
Last updated: 2025/4/18
ABB OT25M4

Selling Points

  • 1Front-operated non-fusible manual switch-disconnector with load-break switch functionality.
  • 2Padlockable handle in the OFF position for enhanced security.
  • 3Rated current of 25A and voltage of 380/400V AC.
  • 4Compact design with dimensions H48mm x W68mm x D73mm.
  • 5Compliant with IEC 60947-3 standards for reliability and safety.
Product Details
OT25M4
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301262D0201
Pollution Degree
3
Product Net Width
68 mm
Product Net Height
48 mm
Product Net Depth / Length
73 mm
Product Net Weight
0.125 kg
Cable Cross-Section
Cu 0.75 ... 10 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 32 A
Conventional Thermal Current (Ithe)
Fully Enclosed 32 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 0.6 W
Rated Conditional Short-Circuit Current (Inc)
(40 A fuse, ≤415V) 50 kA (25 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 25 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 25 A (500 V) 25 A (690 V) 25 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 20 A (500 V) 20 A (690 V) 11 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 4 kW (400 ... 415 V) 9 kW (500 V) 9 kW (690 V) 9 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 0.5 kA
Special Functions
No
Standards
IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Switches Operating Mechanism
Mechanism on Top of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 0.8 N·m
Horsepower Rating UL/CSA
(110 ... 120 V AC) Single Phase 1.5 Hp (240 V AC) Single Phase 3 Hp (440 ... 480 V AC) Single Phase 7.5 Hp (550 ... 600 V AC) Single Phase 10 Hp (220 ... 240 V AC) Three Phase 7,5 Hp (440 ... 480 V AC) Three Phase 15 Hp (550 ... 600 V AC) Three Phase 20 Hp
Tightening Torque
acc. IEC 60947-1 0.8 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Sweden)
3171078
Manufacturer ID
1SCA022497R0650

Specifications may be subject to change without notice