Product Model

OT400DFCC4A

In Stock
Last updated: 2025/4/17
ABB OT400DFCC4A

Selling Points

  • 1Built with robust materials for long-lasting performance.
  • 2Ensures reliable operation in various environments.
  • 3Supports multiple electrical connections for versatility.
  • 4Handles significant electrical loads with ease.
  • 5Easy-to-use and visually distinct for safety.
Product Details
OT400DFCC4A
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
380 mm
Product Net Height
840 mm
Product Net Depth / Length
180 mm
Product Net Weight
14.55 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
II-flange / II-flange
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
Switchable neutral
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
4
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Recommended Screw Driver
Main Circuit M10
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 44 N·m
Recommended Screw Driver
Main Circuit M10
Tightening Torque
Main Circuit 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022745R6710

Specifications may be subject to change without notice