Product Model

OT400DFCC4BA

In Stock
Last updated: 2025/4/18
ABB OT400DFCC4BA

Selling Points

  • 1UV Protected and IP65 Rated: Built to withstand outdoor conditions with UV protection and IP65 rating against low-pressure water jets.
  • 2Padlockable Handles: Secure your switch with padlockable handles, ensuring safety and tamper resistance.
  • 3Rigid Glass Reinforced Polycarbonate Enclosure: Durable and impact-resistant enclosure made from rigid glass reinforced polycarbonate.
  • 4Cable Entries Knock Out Types: Easy cable insertion from top and bottom with knock-out types for II-flanges.
  • 5Interlocked Cover with Defeat Option: Interlocked cover for added safety, with the option to defeat the interlock when necessary.
Product Details
OT400DFCC4BA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
380 mm
Product Net Height
840 mm
Product Net Depth / Length
180 mm
Product Net Weight
13.55 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
II-flange / II-flange
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
0 NO, 0 NC
Neutral Type
Switchable neutral
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Poles
4
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Recommended Screw Driver
Main Circuit M10
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 44 N·m
Recommended Screw Driver
Main Circuit M10
Tightening Torque
Main Circuit 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022834R0880

Specifications may be subject to change without notice