Product Model

OT400DFCC6T

In Stock
Last updated: 2025/4/23
ABB OT400DFCC6T

Selling Points

  • 1Built with UV-resistant materials for long-lasting performance.
  • 2Suitable for both outdoor and indoor use, protected against low-pressure water jets.
  • 3Secure your switch with padlockable handles, ideal for three padlocks.
  • 4Ensures safety with interlocked covers that can be defeated for maintenance.
  • 5Equipped with PE terminals for secure electrical connections.
Product Details
OT400DFCC6T
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
560 mm
Product Net Height
760 mm
Product Net Depth / Length
250 mm
Product Net Weight
27.63 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
2xII-flange / 2xII-flange
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
4 NO, 2 NC
Mounted Auxiliary Contacts
4 NO, 2 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
2
Number of Auxiliary Contacts NO
4
Number of Poles
6P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Position of PE Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Recommended Screw Driver
Main Circuit M10
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 44 N·m
Recommended Screw Driver
Main Circuit M10
Tightening Torque
Main Circuit 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642417
Manufacturer ID
1SCA022277R0650

Specifications may be subject to change without notice