Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
22.01 kg
Cable Entry Position
Up/Down
Cable Outlets Per Side
Open / Open
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 4pcs, 25…120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
0 NO, 0 NC
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Position of Neutral Terminals
Top In - Bottom Out
Position of PE Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Impulse Withstand Voltage (Uimp)
15 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Standards
IEC 60947-1, -3
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022302R8760

Specifications may be subject to change without notice