Product Model
OT400DLRR3TZ

Selling Points
- 1High-Performance and Reliable: Designed for demanding industrial applications with a robust galvanized steel enclosure.
- 2IP65 Protection: Offers excellent protection against dust and water jets, ensuring safe operation in harsh environments.
- 3Padlockable Handle: Securely lockable handle for added safety, preventing accidental operation.
- 4Versatile Cable Entry: Supports various cable configurations including top/bottom, bottom/bottom, and ring-flange types.
- 5Comprehensive Safety Features: Includes gas pressure relief, cover interlocks, and earthed hinges for enhanced user protection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
Product Net Width | 400 mm | Product Net Height | 800 mm |
Product Net Depth / Length | 230 mm | Product Net Weight | 25.55 kg |
Cable Entry Position | Top/Bottom | Cable Outlets Per Side | 4xring-flange / 4xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm |
Connecting Capacity Main Circuit | Hole Diameter 10 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm² | Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
Handle Color | Black | Handle Type | Pistol handle |
Impact Resistance Rating | Housing IK09 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
Mounted Auxiliary Contacts | 2 NO, 1 NC | Neutral Type | No neutral terminal |
Number of Auxiliary Contacts NC | 1 | Number of Auxiliary Contacts NO | 2 |
Number of Poles | 3P | Pollution Degree | 3 |
Position of Line Terminals | Top In - Bottom Out | Position of PE Terminals | Top In - Bottom Out |
Power Loss | at Rated Operating Conditions per Pole 10 W | Rated Conditional Short-Circuit Current (Inc) | 61.5 kA |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A |
Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW |
Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 65 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kA | Recommended Screw Driver | Main Circuit M10 |
Standards | IEC 60947-1, -3 | Tightening Torque | Main Circuit 44 N·m |
Recommended Screw Driver | Main Circuit M10 | Tightening Torque | Main Circuit 44 N·m |
Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | E-Number (Finland) | 3642709 |
E-Number (Norway) | 1429132 | E-Number (Sweden) | 3140632 |
Manufacturer ID | 1SCA022340R1910 |
Specifications may be subject to change without notice