Product Model

OT400DTRR6TZ

In Stock
Last updated: 2025/4/27
ABB OT400DTRR6TZ

Selling Points

  • 1Durable and resistant to corrosion.
  • 2Suitable for outdoor use with protection against UV light.
  • 3High level of protection against dust and water.
  • 4Ensures user safety in case of internal arc.
  • 5Secure with up to 3 padlocks for added safety.
Product Details
OT400DTRR6TZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
42.34 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
8xring-flange / 8xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 8pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
4 NO, 2 NC
Mounted Auxiliary Contacts
4 NO, 2 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
2
Number of Auxiliary Contacts NO
4
Number of Poles
6P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Recommended Screw Driver
Main Circuit M10
Special Functions
EMC
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 44 N·m
Recommended Screw Driver
Main Circuit M10
Tightening Torque
Main Circuit 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3601728
Manufacturer ID
1SCA022545R7790

Specifications may be subject to change without notice