Product Model

OT400E04

In Stock
Last updated: 2025/4/27
ABB OT400E04

Selling Points

  • 1High current capacity: Handles substantial electrical loads effectively.
  • 2Safe disconnection: Ensures secure operation with durable construction and advanced safety features.
  • 3Flexible installation: DIN rail mountable and can be installed in any direction with various mounting options.
  • 4Improved usability: Specially integrated ground disconnects with floor mounting options and 90° rotated control.
  • 5High performance: Suitable for critical applications with reduced design time and space requirements.
Product Details
OT400E04
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301266D0201
Pollution Degree
3
Product Net Width
235 mm
Product Net Height
185 mm
Product Net Depth / Length
107 mm
Product Net Weight
3.5 kg 7.7 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 400 A
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
16000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 132 kW (400 ... 415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 04 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA022727R8000

Specifications may be subject to change without notice