Product Model

OT400ERRR6TZ

In Stock
Last updated: 2025/4/23
ABB OT400ERRR6TZ

Selling Points

  • 1Rigid acid-proof steel enclosure (AISI316L) for durability.
  • 2Hinged door with door lock and interlock function for enhanced safety.
  • 3Gas pressure relief function to protect users in case of internal arc.
  • 4Suitable for both outdoor and indoor applications.
  • 5Includes PE terminals and auxiliary contacts for versatile use.
Product Details
OT400ERRR6TZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
46.14 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
8xring-flange+ø25.5mm / 8xring-flange+ø25.5mm
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 8pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Stainless steel
Handle Color
Stainless Steel
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
4 NO, 2 NC
Mounted Auxiliary Contacts
4 NO, 2 NC
Number of Auxiliary Contacts NC
2
Number of Auxiliary Contacts NO
4
Number of Poles
6P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Recommended Screw Driver
Main Circuit M10
Special Functions
EMC
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 44 N·m
Recommended Screw Driver
Main Circuit M10
Tightening Torque
Main Circuit 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642126
Manufacturer ID
1SCA102329R1001