Product Model

OT400ES04

In Stock
Last updated: 2025/4/23
ABB OT400ES04

Selling Points

  • 1High-performance switch-disconnector for low-voltage applications.
  • 24-pole operation with side-mounted design for easy access.
  • 3Robust safety features including IP00 degree of protection.
  • 4Compatible with a wide range of voltage ratings up to 1000 V.
  • 5Includes terminal bolt kit for secure connections.
Product Details
OT400ES04
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301266D0201
Pollution Degree
3
Product Net Width
270 mm
Product Net Height
185 mm
Product Net Depth / Length
107 mm
Product Net Weight
3.9 kg 8.7 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 400 A
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
16000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Side operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
(500 A fuse, 500 V) 100 kA (500 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 132 kW (400 ... 415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 04 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661715
Manufacturer ID
1SCA022860R1940

Specifications may be subject to change without notice