Product Model

OT400U22

In Stock
Last updated: 2025/4/18
ABB OT400U22

Selling Points

  • 1High Performance: Designed for flexibility and high performance in compact sizes.
  • 2Safety Features: Finger-proof design and wielded contact protection for improved safety.
  • 3Versatile Mounting: Mountable in any position, including Din Rail, door, or base mount.
  • 4Broad Range of Accessories: Compatible with a wide range of accessories for various installations.
  • 5UL and CSA Approvals: Meets UL E63822 and CSA LR58247 standards for reliability and safety.
Product Details
OT400U22
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301266D0201
Pollution Degree
3
Product Net Width
280 mm
Product Net Height
220 mm
Product Net Depth / Length
105 mm
Product Net Weight
3.8 kg 8.3 lb
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
16000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Special Functions
No
Standards
IEC 60947-3 / UL 98 / CSA C22.2 NO.4
Switches Operating Mechanism
Mechanism Between the Poles 22 (Between the Poles)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 42.4 N·m
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
400 A
Horsepower Rating UL/CSA
(acc. to UL 200 V) 100 Hp (acc. to UL 208 V) 100 Hp (acc. to UL 240 V) 125 Hp (acc. to UL 480 V) 250 Hp (acc. to UL 600 V) 350 Hp
Tightening Torque
acc. IEC 60947-1 42.4 N·m
Tightening Torque UL/CSA
375 in·lb
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA022762R7110

Specifications may be subject to change without notice