Product Model

OT630KUUR3TZ-L29

In Stock
Last updated: 2025/4/26
ABB OT630KUUR3TZ-L29

Selling Points

  • 1Designed to meet stringent EMC standards, ensuring reliable operation in harsh electrical environments.
  • 2Suitable for a wide range of applications requiring high current and power handling.
  • 3Durable and resistant to UV light, ideal for outdoor use.
  • 4Provides additional control and safety features with its built-in auxiliary contact.
  • 5Ensures protection against dust and water ingress, enhancing safety and reliability.
Product Details
OT630KUUR3TZ-L29
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
1000 mm
Product Net Depth / Length
230 mm
Product Net Weight
53 kg
Cable Entry Position
Down/Down
Cable Outlets Per Side
Blank / 8xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 8pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 570 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Enclosure Type
MSC
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mechanical Durability
10000
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Bottom In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 25 W
Rated Conditional Short-Circuit Current (Inc)
90 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 570 A (500 V) 570 A (690 V) 570 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 570 A (500 V) 570 A (690 V) 570 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 315 kW (500 V) 400 kW (690 V) 560 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 80 kA
Standards
IEC 60947-1, -3
Terminal Type
Bolt
Tightening Torque
acc. IEC 60947-1 75 N·m
Tightening Torque
acc. IEC 60947-1 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA153773R1001