Product Model

OT63FT4N2

In Stock
Last updated: 2025/4/20
ABB OT63FT4N2

Selling Points

  • 14-pole, front operated, door mounted switch-disconnector with protected clamp terminals.
  • 2High reliability and safety standards compliant with IEC 60947-3, UL 508, and CSA C22.2 No. 14.
  • 3Rated operational current AC-21A: 63 A at 380-415 V, 63 A at 500 V, and 63 A at 690 V.
  • 4Conventional thermal current fully enclosed: 63 A at Θ = 40 °C.
  • 5Modular design for faster and more flexible installation in low voltage systems.
Product Details
OT63FT4N2
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301263D0201
Pollution Degree
3
Product Net Width
70 mm
Product Net Height
72 mm
Product Net Depth / Length
69 mm
Product Net Weight
0.32 kg
Cable Cross-Section
Cu 1.5 ... 35 mm²
Connecting Capacity Main Circuit
Flexible with Ferrule 1x Cu 1.5…4 mm² Solid 1x Cu 1.5…6 mm² Flexible 1x Cu 1.5…35 mm² Stranded 1x Cu 1.5…35 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 63 A
Conventional Thermal Current (Ithe)
Fully Enclosed 63 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Door mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 2.8 W
Rated Conditional Short-Circuit Current (Inc)
(100 A fuse, ≤415 V) 50 kA (100 A fuse, 500 V) 100 kA (80 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 63 A (500 V) 63 A (690 V) 63 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 63 A (500 V) 63 A (690 V) 63 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 63 A (500 V) 45 A (690 V) 20 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 11 kW (400 ... 415 V) 22 kW (500 V) 22 kW (690 V) 15 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 2.1 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 1.5 kA
Recommended Screw Driver
Main Circuit Pozidriv 2
Special Functions
No
Standards
IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Switches Operating Mechanism
Mechanism on Top of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 2 N·m
Wire Stripping Length
Main Circuit 10-12 mm
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
60 A
Horsepower Rating UL/CSA
(110 ... 120 V AC) Single Phase 2 Hp (240 V AC) Single Phase 7.5 Hp (440 ... 480 V AC) Single Phase 15 Hp (550 ... 600 V AC) Single Phase 15 Hp (220 ... 240 V AC) Three Phase 15 Hp (440 ... 480 V AC) Three Phase 30 Hp (550 ... 600 V AC) Three Phase 30 Hp
Wire Stripping Length
Main Circuit 10-12 mm
Recommended Screw Driver
Main Circuit Pozidriv 2
Tightening Torque
acc. IEC 60947-1 2 N·m
Tightening Torque UL/CSA
18 in·lb
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601456
E-Number (Norway)
4363541
E-Number (Sweden)
3171085
Manufacturer ID
1SCA105393R1001

Specifications may be subject to change without notice