Product Model

OT800E03P

In Stock
Last updated: 2025/4/25
ABB OT800E03P

Selling Points

  • 1High current rating of 800A for demanding electrical applications.
  • 2Front-operated design for accessible and convenient power control.
  • 3IP65 protection ensures dust-tight and water-resistant design.
  • 4Meets stringent safety standards with IEC 60947-3 compliance.
  • 5Base-mounted with mechanical durability of 10,000 cycles.
Product Details
OT800E03P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301232D0201
Pollution Degree
3
Product Net Width
266 mm
Product Net Height
250 mm
Product Net Depth / Length
140 mm
Product Net Weight
6.4 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 800 A
Conventional Thermal Current (Ithe)
Fully Enclosed 800 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
10000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 40 W
Rated Conditional Short-Circuit Current (Inc)
(800 A fuse, 500 V) 100 kA (800 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 250 kW (400 ... 415 V) 450 kW (500 V) 560 kW (690 V) 800 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 03 (Left Side)
Terminal Type
Lug terminals
Terminal Width
39 mm
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5293 >> Switch disconnector
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3660784
E-Number (Norway)
4337098
E-Number (Sweden)
3171226
Manufacturer ID
1SCA022718R9410

Specifications may be subject to change without notice