ABB OT800E11P

Selling Points

  • 1High-capacity 800A current rating for robust electrical isolation.
  • 2Durable construction for long-lasting performance in industrial settings.
  • 3Advanced safety features for reliable disconnection during maintenance or emergencies.
  • 4Compact design for easy integration into switchgear systems.
  • 5Meets stringent industry standards for reliability and safety.
Product Details
OT800E11P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301232D0201
Pollution Degree
3
Product Net Width
201 mm
Product Net Height
250 mm
Product Net Depth / Length
140 mm
Product Net Weight
4.4 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 800 A
Conventional Thermal Current (Ithe)
Fully Enclosed 800 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
10000
Mounting Type
Base mounting
Number of Poles
2P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 40 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A (1000 V) 800 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 250 kW (400 ... 415 V) 450 kW (500 V) 560 kW (690 V) 800 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism Between the Poles 11 (Between the Poles)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)