Product Model

OT800KFCC4BA

In Stock
Last updated: 2025/4/18
ABB OT800KFCC4BA

Selling Points

  • 1Built with a rigid glass-reinforced polycarbonate enclosure, ensuring high impact strength and UV protection.
  • 2Protected against low-pressure water jets, making it suitable for both outdoor and indoor applications.
  • 3Cable entries are knock-out types for II-flanges, allowing insertion from top and bottom.
  • 4Padlockable handle with space for three padlocks, ensuring secure operation.
  • 5Interlocked cover that can be defeated, providing additional safety features.
Product Details
OT800KFCC4BA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
560 mm
Product Net Height
760 mm
Product Net Depth / Length
250 mm
Product Net Weight
27.83 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
2xII-flange / 2xII-flange
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 720 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
0 NO, 0 NC
Neutral Type
Switchable neutral
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Poles
4
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 40 W
Rated Conditional Short-Circuit Current (Inc)
90 kA
Rated Impulse Withstand Voltage (Uimp)
20 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 720 A (690 V) 720 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 720 A (500 V) 720 A (690 V) 720 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 400 kW (500 V) 500 kW (690 V) 710 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Recommended Screw Driver
Main Circuit M12
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 75 N·m
Recommended Screw Driver
Main Circuit M12
Tightening Torque
Main Circuit 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022834R1180

Specifications may be subject to change without notice