Product Model

OT80F3/B50

In Stock
Last updated: 2025/4/21
ABB OT80F3/B50

Selling Points

  • 1High Voltage Rating: 600 VAC for reliable operation in industrial settings.
  • 2High Current Capacity: 80 A to handle demanding electrical loads.
  • 3Three Pole Design: Suitable for three-phase applications, enhancing efficiency and safety.
  • 4UL508 and NF Standards: Meets stringent safety standards for electrical equipment in North America and Europe.
  • 5Durable Construction: Built with mechanical durability and IP20 protection for long-lasting performance.
Product Details
OT80F3/B50
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301263D0201
Pollution Degree
3
Product Net Width
52.5 mm
Product Net Height
91.5 mm
Product Net Depth / Length
72.5 mm
Product Net Weight
13 kg
Cable Cross-Section
Cu 1.5 ... 35 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 80 A
Degree of Protection
Front IP20
Handle Type
Knob Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Number of Poles
3P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 4.5 W
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 75 A (500 V) 58 A (690 V) 20 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 22 kW (400 ... 415 V) 37 kW (500 V) 37 kW (690 V) 18.5 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 2.1 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 1.5 kA
Standards
IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 2 N·m
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
80 A
Horsepower Rating UL/CSA
(110 ... 120 V AC) Single Phase 2 Hp (240 V AC) Single Phase 10 Hp (440 ... 480 V AC) Single Phase 20 Hp (550 ... 600 V AC) Single Phase 20 Hp (220 ... 240 V AC) Three Phase 20 Hp (440 ... 480 V AC) Three Phase 40 Hp (550 ... 600 V AC) Three Phase 40 Hp
Tightening Torque
acc. IEC 60947-1 2 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601459
Manufacturer ID
1SCA126086R1001

Specifications may be subject to change without notice