Selling Points

  • 1Rated for 125A permanent current and 45 kW operation power at 400V.
  • 2Equipped with inbuilt safety features and interlockable design for enhanced security.
  • 3Suitable for floor and front mounting with a compact size of 100mm height, 230mm width, and 116mm depth.
  • 4Can be operated manually in emergency situations, ensuring continuous functionality.
  • 5Built-in device with a mechanical endurance of 20,000 operation cycles.
Product Details
OTM125F3M230V
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
160 mm
Product Net Height
100 mm
Product Net Depth / Length
116 mm
Product Net Weight
0.9 kg
Cable Cross-Section
Cu 10 ... 70 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 125 A
Conventional Thermal Current (Ithe)
Fully Enclosed 125 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
20000
Motor Operational Voltage
110 ... 240 V AC/DC
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 6.3 W
Rated Conditional Short-Circuit Current (Inc)
(125 A fuse, 415 V) 50 kA (125 A fuse, 690 V) 18 kA (63 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 90 A (500 V) 70 A (690 V) 50 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 22 kW (400 ... 415 V) 45 kW (500 V) 45 kW (690 V) 45 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 3.6 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 2.5 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 6 N·m
Tightening Torque
acc. IEC 60947-1 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA122968R1001

Specifications may be subject to change without notice