Product Model

OTM250E4CM110V

In Stock
Last updated: 2025/4/23
ABB OTM250E4CM110V

Selling Points

  • 1Built with durable materials for long-lasting performance.
  • 2Includes a handle for manual operation and bolt kit with nut and washers for all terminals.
  • 3Features an integrated motor drive for efficient switching operations.
  • 4Offers IP20 protection, ensuring a safe and reliable electrical environment.
  • 5Suitable for front mounting 4-hole and distribution board installation, enhancing flexibility in setup.
Product Details
OTM250E4CM110V
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC303036D0202
Pollution Degree
3
Product Net Width
307 mm 12.09 in
Product Net Height
150 mm 5.91 in
Product Net Depth / Length
197 mm 7.76 in
Product Net Weight
5 kg 11.02 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Motor Operational Voltage
110 ... 125 V AC/DC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 250 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 140 kW (500 V) 170 kW (690 V) 250 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Transition Type
Open
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3641737
Manufacturer ID
1SCA022846R1830

Specifications may be subject to change without notice