Selling Points

  • 1Supports up to 315 A at 380-415 V, 500 V, and 690 V.
  • 2Meets IEC 60947 standards with a rated insulation voltage of 1000 V and a short-circuit making capacity of 15 kA.
  • 3Dimensions: 298 mm x 185 mm x 211.5 mm, weighing 7.6 kg.
  • 4Includes a handle for manual operation and is designed for motorized control.
  • 5Compliant with RoHS, CE, and ATEX standards, ensuring environmental and safety compliance.
Product Details
OTM315E3M230C
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Pollution Degree
3
Product Net Width
298 mm
Product Net Height
185 mm
Product Net Depth / Length
211.5 mm
Product Net Weight
7.6 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 315 A
Conventional Thermal Current (Ithe)
Fully Enclosed 315 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
16000
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
(500 A fuse, 500 V) 100 kA (500 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 315 A (500 V) 315 A (690 V) 315 A (1000 V AC) 315 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 315 A (500 V) 315 A (690 V) 315 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 315 A (500 V) 315 A (690 V) 315 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 100 kW (400 ... 415 V) 160 kW (500 V) 220 kW (690 V) 315 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA115334R1001

Specifications may be subject to change without notice