Product Model

OTM400E4M230C

In Stock
Last updated: 2025/4/22
ABB OTM400E4M230C

Selling Points

  • 1Supports up to 400 A at 380-415 V AC.
  • 2Equipped with comprehensive inbuilt safety features for secure operation.
  • 3Designed for durability with a weight of 8.7 kg and dimensions of 386 mm x 185 mm x 211.5 mm.
  • 4Can be operated manually in emergency situations.
  • 5Meets IEC 60947-3 standards for switch-disconnectors.
Product Details
OTM400E4M230C
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Pollution Degree
3
Product Net Width
386 mm
Product Net Height
185 mm
Product Net Depth / Length
211.5 mm
Product Net Weight
8.7 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 400 A
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
16000
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
(500 A fuse, 500 V) 100 kA (500 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A (1000 V AC) 400 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 132 kW (400 ... 415 V) 220 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Tightening Torque
acc. IEC 60947-1 30 … 44 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA115336R1001

Specifications may be subject to change without notice