Product Model

OTM630E2M230V

In Stock
Last updated: 2025/4/27
ABB OTM630E2M230V

Selling Points

  • 1Equipped with comprehensive inbuilt safety features for secure operation.
  • 2Supports up to 630 A operational current for heavy-duty applications.
  • 3Compact size with dimensions (WxHxD/L) 350 mm x 250 mm x 312 mm.
  • 4Can be operated manually in emergency situations.
  • 5Meets IEC 60947 technical standards for reliability and safety.
Product Details
OTM630E2M230V
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC303036D0202
Pollution Degree
3
Product Net Width
350 mm
Product Net Height
250 mm
Product Net Depth / Length
312 mm
Product Net Weight
8.3 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 630 A
Conventional Thermal Current (Ithe)
Fully Enclosed 630 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
10000
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
2P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 25 W
Rated Conditional Short-Circuit Current (Inc)
(800 A fuse, 500 V) 100 kA (800 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A (1000 V AC) 630 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 200 kW (400 ... 415 V) 355 kW (500 V) 400 kW (690 V) 630 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601505
Manufacturer ID
1SCA121190R1001

Specifications may be subject to change without notice