Product Model

OTM800E4M230C

In Stock
Last updated: 2025/4/21
ABB OTM800E4M230C

Selling Points

  • 1High-performance motorized switch-disconnector for reliable operation.
  • 2Compact design with a uniquely short current path for efficient use.
  • 3Robust safety features including inbuilt safety mechanisms and manual operation in emergencies.
  • 4Suitable for diverse applications with AC and DC ratings up to 800 Amperes.
  • 5Meets IEC 60947-1 and 60947-3 standards for technical reliability and safety.
Product Details
OTM800E4M230C
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Pollution Degree
3
Product Net Width
480 mm
Product Net Height
250 mm
Product Net Depth / Length
312 mm
Product Net Weight
14.9 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 800 A
Conventional Thermal Current (Ithe)
Fully Enclosed 800 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
10000
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 40 W
Rated Conditional Short-Circuit Current (Inc)
(800 A fuse, 500 V) 100 kA (800 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A (1000 V AC) 800 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 250 kW (400 ... 415 V) 450 kW (500 V) 560 kW (690 V) 800 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3638153
Manufacturer ID
1SCA115356R1001

Specifications may be subject to change without notice