Product Model

OTM80F4CMA230V

In Stock
Last updated: 2025/4/24
ABB OTM80F4CMA230V

Selling Points

  • 1High reliability with a robust design for demanding environments.
  • 2Efficient operation with a direct mount handle and base mounting.
  • 3Includes a bolt kit with nut and washers for all terminals and male connectors for control circuits.
  • 4Compliant with EU Directive 2011/65/EU and Amendment 2015/863, ensuring safety standards.
  • 5Suitable for 80A, 4P applications with a maximum voltage of 800V and current of 80A.
Product Details
OTM80F4CMA230V
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
283 mm 11.14 in
Product Net Height
100 mm 3.94 in
Product Net Depth / Length
116 mm 4.57 in
Product Net Weight
1.86 kg 4.1 lb
Cable Cross-Section
10 ... 70 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 80 A
Conventional Thermal Current (Ithe)
Fully Enclosed 80 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Motor Operational Voltage
110 ... 240 V AC/DC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 3.5 W
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 80 A (500 V) 60 A (690 V) 40 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 80 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 80 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 37 kW (500 V) 37 kW (690 V) 37 kW
Rated Operational Voltage
Main Circuit 800 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 2.5 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 6 N·m
Transition Type
Open
Tightening Torque
acc. IEC 60947-1 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122214
IDEA Granular Category Code (IGCC)
5208 >> Controller switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601235
Manufacturer ID
1SCA120100R1001