Product Model
S201M-C25UC

Selling Points
- 1The S201M-C25UC boasts a rated short-circuit capacity of 10 kA across various voltages, ensuring reliable protection.
- 2Suitable for both DC and AC applications, this MCB offers flexibility in a wide range of electrical systems.
- 3Meets IEC/EN 60898-2 and IEC/EN 60947-2 standards, ensuring global compatibility and safety.
- 4Compatible with all current System pro M compact accessories, simplifying installation and maintenance.
- 5Designed to withstand 20,000 electrical cycles and 25g shock resistance, ensuring long-lasting performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Standards | IEC/EN 60898-2 IEC/EN 60947-2 | Tripping Characteristic | C |
Rated Operational Voltage | acc. to IEC 60898-1 220 V DC acc. to IEC 60898-1 230 V AC acc. to IEC 60898-1 220 V acc. to IEC 60898-2 220 V DC acc. to IEC 60898-2 230 V AC acc. to IEC 60947-2 253 V AC acc. to IEC 60947-2 220 V DC | Operational Voltage | Maximum (Incl. Tolerance) 250 V DC Maximum (Incl. Tolerance) 253 V AC Minimum 12 V AC Minimum 12 V DC |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V | Rated Impulse Withstand Voltage (Uimp) | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
Dielectric Test Voltage | 50/60 Hz-1 min: 2 kV | Input Voltage Type | AC/DC |
Rated Current (In) | 25 A | Rated Short-Circuit Capacity | (AC) 10 kA (220 V DC) 10 kA (230 / 400 V AC) 10 kA (230 V AC) 10 kA (253 V DC) 10 kA (230 V) 10 kA (400 V) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (110 V DC) 20 kA (220 V DC) 10 kA (230 V AC) 10 kA (253 V AC) 10 kA (230 V) 10 kA | Rated Conditional Short-Circuit Current (Inc) | (230 V) 10 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (110 V DC) 10 kA | Rated Frequency (f) | 50 / 60 Hz DC |
Power Loss | 2.62 W at Rated Operating Conditions per Pole 2.62 W | Power Supply Connection | Please Note Polarity of Device |
Contact Position Indication | Red ON / Green OFF | Energy Limiting Class | 3 |
Electrical Endurance | 20000 AC cycle | Mechanical Endurance | 20000 cycle |
Number of Protected Poles | 1 | Number of Poles | 1 |
Overvoltage Category | III | Tightening Torque | 2.8 N·m |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal | Actuator Marking | I / O |
Actuator Material | Insulation Group II, Black, Sealable | Housing Material | Insulation Group I, RAL 7035 |
Options Provided | Universal current | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position | any | Recommended Screw Driver | Pozidriv 2 |
Accessories Available | Yes | Remarks | Please note polarity of device |
Connecting Capacity | Busbar 10 / 10 mm² Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm² | Installation Size | acc. to DIN 43880 1 |
Terminal Type | Screw Terminals | Ambient Air Temperature | Operation -25 ... +55 °C Storage -40 ... +70 °C |
Reference Ambient Air Temperature | 30 °C | Degree of Protection | IP20 Enclosure with Cover IP40 |
Pollution Degree | 3 | Environmental Conditions | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz | Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
Environmental Information | 2CDK400030D201 | Maximum Operating Voltage UL/CSA | 250 V DC 480Y/277 V AC |
Interrupting Rating acc. to UL1077 | (110 V DC) 10 kA (220 V AC) 10 kA (250 V DC) 10 kA (253 V AC) 6 kA (480Y / 277 V AC) 10 kA | Connecting Capacity UL/CSA | Busbar 14-8 AWG Conductor 14-4 AWG |
Tightening Torque UL/CSA | 25 in·lb | Width in Number of Modular Spacings | 1.0 |
Product Net Width | 17.5 mm | Product Net Height | 85 mm |
Product Net Depth / Length | 69 mm | Product Net Weight | 0.125 kg |
Pole Net Weight | 0.125 kg | Built-In Depth (t2) | 69 mm |
ETIM 8 | EC000042 - Miniature circuit breaker (MCB) | ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | WEEE B2C / B2B | Business To Business |
CN8 | 8536 20 10 | UNSPSC | 39121603 |
eClass | V11.0 : 27141901 | IDEA Granular Category Code (IGCC) | 4899 >> Miniature circuit breaker (MCB) screw-in model |
Object Classification Code | F | Manufacturer ID | 2CDS271061R0254 |
Specifications may be subject to change without notice