Product Model
S201M-C63GRID

Selling Points
- 1Advanced tripping mechanisms for overload and short circuit protection.
- 2Compliant with IEC/EN 60898-1 and IEC/EN 60947-2 standards.
- 3Available in different characteristics (B, C, D, K, Z) and configurations (1P, 1P+N, 2P, 3P, 3P+N, 4P).
- 4High breaking capacities up to 10 kA at 230/400 V AC.
- 5Compact design with bottom-fitting auxiliary contact to save 50% space.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Standards | IEC/EN 60898-1 CSA 22.2 No. 235 IEC/EN 60947-2 UL 1077 | Tripping Characteristic | C |
Rated Operational Voltage | acc. to IEC 60898-1 230 V AC acc. to IEC 60898-1 230 V acc. to IEC 60947-2 230 V AC | Operational Voltage | Maximum (Incl. Tolerance) 253 V AC Maximum (Incl. Tolerance) 72 V DC |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V | Rated Impulse Withstand Voltage (Uimp) | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
Input Voltage Type | AC/DC | Rated Current (In) | 63 A |
Rated Short-Circuit Capacity | (230 V AC) 10 kA (400 V AC) 10 kA (230 V) 10 kA (400 V) 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (133 V AC) 25 kA (230 V) 15 kA (400 V) 15 kA |
Rated Conditional Short-Circuit Current (Inc) | (230 V) 15 kA (400 V) 15 kA | Rated Service Short-Circuit Breaking Capacity (Ics) | (133 V AC) 15 kA (230 V AC) 10 kA |
Rated Frequency (f) | 50 / 60 Hz | Power Loss | 4.8 W at Rated Operating Conditions per Pole 4.8 W |
Power Supply Connection | Arbitrary | Energy Limiting Class | 3 |
Number of Protected Poles | 1 | Number of Poles | 1 |
Overvoltage Category | III | Tightening Torque | 2.8 N·m |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal | Actuator Marking | I / O |
Mounting Position | any | Accessories Available | Yes |
Connecting Capacity | Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm² | Terminal Type | Screw Terminals |
Ambient Air Temperature | Operation -25 ... +55 °C | Degree of Protection | IP20 IP40 |
Pollution Degree | 3 | Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms | Tightening Torque UL/CSA | 18 in·lb |
Width in Number of Modular Spacings | 1.0 | Product Net Width | 17.5 mm |
Product Net Height | 88 mm | Product Net Depth / Length | 69 mm |
Product Net Weight | 135 g | Pole Net Weight | 0.125 kg |
Built-In Depth (t2) | 69 mm | Dimension Diagram | 2CDC022007F0010 |
ETIM 8 | EC000042 - Miniature circuit breaker (MCB) | ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | WEEE B2C / B2B | Business To Business |
CN8 | 8536 20 10 | UNSPSC | 39121603 |
eClass | V11.0 : 27141901 | IDEA Granular Category Code (IGCC) | 4897 >> Miniature circuit breakers |
Manufacturer ID | 2CDS271301R0634 |
Specifications may be subject to change without notice