Product Model

T4L250 PR221DS-LS/I In100 4p FFC 1000VAC

In Stock
Last updated: 2025/4/19
ABB T4L250 PR221DS-LS/I In100 4p FFC 1000VAC

Selling Points

  • 1High performance and reliability in industrial settings.
  • 2Compliant with IEC 60947 standards for safety and efficiency.
  • 3Suitable for 1000V AC applications with a rated current of 100A.
  • 4Durable design with 8000 electrical cycles and 20000 mechanical cycles.
  • 5Solid-state release mechanism for precise control and safety.
Product Details
T4L250 PR221DS-LS/I In100 4p FFC 1000VAC
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1057 9AKK108467A6707
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.05 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 1.7 W
Rated Current (In)
100 A
Rated Operational Voltage
1000 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(1000 V AC) 12 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(415 V AC) 120 kA (1000 V AC) 12 kA
Rated Uninterrupted Current (Iu)
250 A
Release
PR221DS-LS/I
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T4
Terminal Connection Type
Fixed Circuit-Breakers Front for Copper Cables
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA063418R1

Specifications may be subject to change without notice