Product Model

T4L 250 TMA 200-2000 4p F F InN=100%In

In Stock
Last updated: 2025/4/19
ABB T4L 250 TMA 200-2000 4p F F InN=100%In

Selling Points

  • 1High performance in industrial settings with thermomagnetic release.
  • 2Four-pole configuration for enhanced reliability and efficiency.
  • 3Front terminal connections for easy installation and maintenance.
  • 4Rated for 200-2000 A current range, suitable for various applications.
  • 5Meets IEC 60947 standards for safety and reliability.
Product Details
T4L 250 TMA 200-2000 4p F F InN=100%In
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1057
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.05 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T4
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
20000 cycle 240 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 9.9 W
Rated Current (In)
200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V) 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 70 kA (750 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T4
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA054285R1

Specifications may be subject to change without notice