Product Model
T4L 250 UL/CSA TMA 100-500..1000 3p F F

Selling Points
- 1High interrupting capacity up to 1000 A for reliable short-circuit protection.
- 2Compliant with UL and CSA standards for safety and regulatory compliance.
- 3Thermal-magnetic trip units (TMA) provide precise and adjustable thermal and magnetic thresholds.
- 4Compact size with dimensions of 5.12 in x 3.54 in x 2.76 in for easy installation.
- 5Suitable for 3-pole applications with fixed terminals for versatile electrical distribution needs.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Weight | 1 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | CB |
Version | F | Mechanical Durability | 20000 cycle |
Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 5.2 W |
Rated Current (In) | 100 A | Rated Operational Voltage | 600 V AC 600 V DC |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 65 kA (500 V DC) 2 Poles in Series 65 kA (600 V DC) 3 Poles in Series 50 kA | Rated Uninterrupted Current (Iu) | 250 A |
Release | TMA | Release Type | TM |
Short-Circuit Performance Level | L | Standards | UL 489 CSA C22.2 |
Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
Test Voltage Max (Utest) | 3500 V | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SDA058136R1 |
Specifications may be subject to change without notice