Product Model
T4V 250 PR222DS/P-LSI In=250 3p F F

Selling Points
- 1Withstand short-circuit currents up to 200 kA at 220V AC and 180 kA at 440V AC.
- 2Ensures reliable and fast operation with a solid-state release mechanism.
- 3Convenient front terminal connection for easy installation and maintenance.
- 4Meets EU Directive 2011/65/EU and Amendment 2015/863 for environmental compliance.
- 5Operates at rated voltages from 220V AC to 690V AC, making it versatile for various applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1057 | Product Net Width | 105 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 3.5 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T4 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 8000 cycle 120 cycles per hour |
Mechanical Durability | 20000 cycle 240 cycles per hour | Number of Poles | 3 |
Power Loss | at Rated Operating Conditions per Pole 10.7 W | Rated Current (In) | 250 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V) 150 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V AC) 80 kA | Rated Uninterrupted Current (Iu) | 250 A |
Release | PR222DS/P-LSI | Release Type | EL |
Short-Circuit Performance Level | V | Standards | IEC |
Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
Test Voltage Max (Utest) | 3500 V | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | UNSPSC | 39121100 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA054101R1 |
Specifications may be subject to change without notice