Product Model
T4V 250 TMA 250-2500 4p F F InN=100%In

Selling Points
- 1High-Performance Design: Engineered for reliability and efficiency in demanding electrical applications.
- 2Thermomagnetic Release: Ensures safe operation with automatic release in case of short circuits.
- 3Rated for 250-2500A: Suitable for a wide range of current requirements, from 250 to 2500 amps.
- 4Four-Pole Configuration: Ideal for applications needing four poles, enhancing flexibility and control.
- 5Compliant with IEC Standards: Meets international safety and performance standards for circuit breakers.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1057 | Product Net Width | 140 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 3.05 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T4 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 8000 cycle 120 cycles per hour |
Mechanical Durability | 20000 cycle 240 cycles per hour | Number of Poles | 4 |
Power Loss | at Rated Operating Conditions per Pole 13.7 W | Rated Current (In) | 250 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V) 150 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V AC) 150 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 70 kA | Rated Uninterrupted Current (Iu) | 250 A |
Release | TMA | Release Type | TM |
Short-Circuit Performance Level | V | Standards | IEC |
Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
Test Voltage Max (Utest) | 3500 V | Test Voltage at Industrial Frequency for 1 Minute | 3500 V |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA054290R1 |
Specifications may be subject to change without notice