Product Model
T4V-HA250 PR222DS-LSIG In250 4p FF800VAC

Selling Points
- 1High Performance: Designed for AC applications up to 800VAC, ensuring reliable operation in demanding electrical environments.
- 2Solid-State Release: Features advanced solid-state release technology for efficient and safe circuit interruption.
- 3Durable Construction: Built to withstand 20,000 electrical cycles and 8,000 mechanical cycles, ensuring long-lasting performance.
- 4Compliance with Standards: Meets IEC 60947 standards, ensuring compliance with international safety and performance requirements.
- 5Versatile Application: Suitable for a wide range of applications, including transformer and generator installations, providing flexibility in electrical system design.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1057 9AKK108467A6707 | Product Net Depth / Length | 108.5 mm |
Product Main Type | SACE Tmax T | Product Name | Moulded case circuit breaker |
Product Type | Switch Disconnector | Version | F |
Current Type | AC | Electrical Durability | 2000 cycle |
Mechanical Durability | 20000 cycle | Number of Poles | 4P |
Power Loss | 14 W | Rated Current (In) | 250 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 800 V | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (800 V AC) 25 kA |
Rated Uninterrupted Current (Iu) | 250 A | Rated Voltage (Ur) | 800 V |
Short-Circuit Performance Level | V | Standards | IEC |
Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front for Copper Cables |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA113740R1 |
Specifications may be subject to change without notice