Product Model
T5L 400 TMA 400-4000 3p F F

Selling Points
- 1High interrupt rating of 200 kA for robust short-circuit protection.
- 2Thermal magnetic trip for reliable and fast overload protection.
- 3Suitable for 3 poles, 400 A, and 690 V AC applications.
- 4Compact dimensions: 103.5 x 140 x 205 mm for easy installation.
- 5Meets IEC standards and is RoHS compliant for environmental safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 140 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 4.8 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3 |
Power Loss | at Rated Operating Conditions per Pole 19.5 W | Rated Current (In) | 400 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 70 kA (750 V DC) 3 Poles in Series 50 kA |
Rated Uninterrupted Current (Iu) | 400 A | Release | TMA |
Release Type | TM | Short-Circuit Performance Level | L |
Standards | IEC | Sub-type | T5 |
Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
Test Voltage at Industrial Frequency for 1 Minute | 3500 V | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA054449R1 |
Specifications may be subject to change without notice