Product Model

T5L 630 BREAKING PART 3p F F

In Stock
Last updated: 2025/4/18
ABB T5L 630 BREAKING PART 3p F F

Selling Points

  • 1High Breaking Capacity: Up to 200 kA at 380/415 V AC for reliable short-circuit protection.
  • 2Advanced Insulation: Ensures no leakage currents and dielectric resistance to overvoltages, meeting IEC 60947-2 standards.
  • 3Versatile Application: Suitable for alternating current networks from 20 A to 1600 A and direct current plants from 20 A to 800 A.
  • 4Durable Construction: Designed with mechanical durability of up to 20,000 cycles and electrical durability of up to 5,000 cycles.
  • 5Comprehensive Protection: Equipped with PR221DS-LS/I solid-state release for enhanced safety and reliability.
Product Details
T5L 630 BREAKING PART 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1056 9AKK108467A6707
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.25 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Breaking Part
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Device
Breaking Part
Electrical Durability
5000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
3
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 70 kA (750 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
630 A
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA054590R1

Specifications may be subject to change without notice