Product Model
T5L 630 Ekip E-LSIG In=630A 3p F F

Selling Points
- 1Measures active, reactive, and apparent energy with high accuracy.
- 2Includes protections against overloads, short-circuits, and earth faults with adjustable thresholds.
- 3Available in three-pole and four-pole versions with manual and electronic setting options.
- 4Equipped with communication function for remote monitoring and control via MODBUS network.
- 5Features LED indicators for pre-alarm and alarm conditions, ensuring timely intervention in case of faults.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 140 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 5.1 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3 |
Rated Current (In) | 630 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA |
Rated Uninterrupted Current (Iu) | 630 A | Release | Ekip E-LSIG |
Release Type | EL | Short-Circuit Performance Level | L |
Standards | IEC | Sub-type | T5 |
Terminal Connection Type | Fixed Circuit-Breakers Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA081066R1 |
Specifications may be subject to change without notice