Product Model

T5L 630 Ekip E-LSIG In=630A 3p F F

In Stock
Last updated: 2025/4/18
ABB T5L 630 Ekip E-LSIG In=630A 3p F F

Selling Points

  • 1Measures active, reactive, and apparent energy with high accuracy.
  • 2Includes protections against overloads, short-circuits, and earth faults with adjustable thresholds.
  • 3Available in three-pole and four-pole versions with manual and electronic setting options.
  • 4Equipped with communication function for remote monitoring and control via MODBUS network.
  • 5Features LED indicators for pre-alarm and alarm conditions, ensuring timely intervention in case of faults.
Product Details
T5L 630 Ekip E-LSIG In=630A 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1056 9AKK108467A6707
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
3
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA
Rated Uninterrupted Current (Iu)
630 A
Release
Ekip E-LSIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA081066R1

Specifications may be subject to change without notice