Product Model

T5L630 PR222DS/P-LSIG In630 3p FF1000VAC

In Stock
Last updated: 2025/4/22
ABB T5L630 PR222DS/P-LSIG In630 3p FF1000VAC

Selling Points

  • 1Up to 120 kA at 380V AC and 100 kA at 440V AC.
  • 2Includes LSI (Low, Short, Instantaneous) protection with adjustable settings via Modbus.
  • 3Built with solid-state release for reliable operation in harsh environments.
  • 4Meets IEC 60947-2 and EC directives for low voltage and electromagnetic compatibility.
  • 5Withstands 20,000 mechanical cycles and 5,000 electrical cycles under load conditions.
Product Details
T5L630 PR222DS/P-LSIG In630 3p FF1000VAC
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1056
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.25 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
1000 cycle
Mechanical Durability
20000 cycle
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 41 W
Rated Current (In)
630 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
1000 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(1000 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(1000 V AC) 12 kA
Rated Uninterrupted Current (Iu)
630 A
Rated Voltage (Ur)
1000 V AC
Release
PR222DS/P-LSIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T5
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA064218R1

Specifications may be subject to change without notice