Product Model
T5N 400 UL/CSA PR221DS-LS/I 400 2p F F

Selling Points
- 1400A rated current for robust power distribution.
- 2Meets UL and CSA standards for global compliance.
- 3Oversized insulation for enhanced safety and reliability.
- 4Designed for 20,000 cycles with a mechanical life of 20000 operations.
- 5Front terminal connection type for straightforward setup.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 140 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 3.25 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Mechanical Durability | 20000 cycle 120 cycles per hour |
Number of Poles | 2 | Rated Current (In) | 400 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 600 V AC | Rated Uninterrupted Current (Iu) | 400 A |
Release | PR221DS-LS/I | Release Type | EL |
Short-Circuit Performance Level | N | Standards | UL |
Sub-type | T5 | Terminal Connection Type | Fixed Circuit-Breakers Front |
Interrupting Rating acc. to UL489 | (240 V AC) 65 kA (480 V AC) 25 kA (600 V AC) 18 kA | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | IDEA Granular Category Code (IGCC) | 4930 >> 2 Pole Non-Interchangeable Trip Electronic Circuit Breakers |
UNSPSC | 39121616 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA064135R1 |
Specifications may be subject to change without notice