Product Model
T5N 400 UL/CSA PR222DS/P-LSIG 400 4p F F

Selling Points
- 1High-Rated Current Capacity: Handles 400A main circuit current.
- 2UL/CSA Certification: Meets UL 489 and CSA standards for safety.
- 3Mechanical Durability: Withstands up to 20,000 cycles at 60 cycles per hour.
- 4Electrical Insulation: Rated for 1000V impulse withstand voltage and 690V AC insulation voltage.
- 5Short-Circuit Performance: Breaks short circuits up to 36kA at rated operational voltages.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 186 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 6.2 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Mechanical Durability | 20000 cycle 120 cycles per hour |
Number of Poles | 4 | Power Loss | at Rated Operating Conditions per Pole 16.5 W |
Rated Current (In) | 400 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 600 V AC |
Rated Uninterrupted Current (Iu) | 400 A | Release | PR222DS/P-LSIG |
Release Type | EL | Short-Circuit Performance Level | N |
Standards | UL | Sub-type | T5 |
Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
Interrupting Rating acc. to UL489 | (240 V AC) 65 kA (480 V AC) 25 kA (600 V AC) 18 kA | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA060454R1 |
Specifications may be subject to change without notice