Product Model

T5N400 UL TMA 300-1500..3000 4p FF N100%

In Stock
Last updated: 2025/4/18
ABB T5N400 UL TMA 300-1500..3000 4p FF N100%

Selling Points

  • 1UL 489 Listed for Enhanced Safety: Meets rigorous safety standards for branch circuit protection.
  • 2100% Neutral Protection: Ensures complete protection against neutral faults.
  • 3Wide Amp Range (15 ~ 2500 Amps): Suitable for a broad range of applications.
  • 4240/277/480/600Y VAC Compatibility: Compatible with various voltage configurations.
  • 5Thermal/Magnetic Trip for Reliable Operation: Combines thermal and magnetic trips for consistent performance.
Product Details
T5N400 UL TMA 300-1500..3000 4p FF N100%
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1056 9AKK108467A6707
Product Net Width
186 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
4.15 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 12.3 W
Rated Current (In)
300 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC 600 V DC
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 65 kA (480 V AC) 25 kA (600 V AC) 18 kA (500 V DC) 2 Poles in Series 25 kA (600 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)
400 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
UL
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 65 kA (480 V AC) 25 kA (600 V AC) 18 kA (500 V DC) 2 Poles in Series 25 kA (600 V DC) 3 Poles in Series 16 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060632R1

Specifications may be subject to change without notice