Product Model
T5S 630 Ekip E-LSIG In=630A 4p F F

Selling Points
- 1Equipped with adjustable protection thresholds for overloads, short-circuits, and instantaneous short-circuits.
- 2Designed to withstand 5000 cycles at 60 cycles per hour and 20,000 cycles at 120 cycles per hour.
- 3Offers comprehensive energy measurement capabilities, including active, reactive, and apparent power.
- 4Features communication function for remote control and monitoring via MODBUS network.
- 5Meets EU RoHS and TSCA compliance standards for environmental safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 186 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 6.2 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
Rated Current (In) | 630 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (690 V AC) 25 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (690 V AC) 25 kA |
Rated Uninterrupted Current (Iu) | 630 A | Release | Ekip E-LSIG |
Release Type | EL | Short-Circuit Performance Level | S |
Standards | IEC | Sub-type | T5 |
Terminal Connection Type | Fixed Circuit-Breakers Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA081069R1 |
Specifications may be subject to change without notice