Product Model
T5V 400 PR221DS-I In=400 4p F FC 1150VAC

Selling Points
- 1Advanced Protection: Instantaneous protection against short-circuits with adjustable settings.
- 2High Current Rating: Rated current of 400A for robust electrical handling.
- 3Multiple Standards Compliance: Meets IEC 60947-2 and EC directives for low voltage and electromagnetic compatibility.
- 4Durable Construction: Designed for 7000 electrical durability cycles and 20000 mechanical durability cycles.
- 5Versatile Application: Suitable for various applications including industrial power distribution systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 184 mm |
Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 6.2 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4P |
Power Loss | at Rated Operating Conditions per Pole 16.5 W | Rated Current (In) | 400 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1150 V |
Rated Operational Voltage | 1150 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (1000 V AC) 10 kA (1150 V AC) 6 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (1000 V AC) 20 kA (1150 V AC) 12 kA |
Rated Uninterrupted Current (Iu) | 400 A | Release | PR221DS-I |
Release Type | EL | Short-Circuit Performance Level | V |
Standards | IEC | Sub-type | T5 |
Terminal Connection Type | Fixed Circuit-Breakers Front for Copper Cables | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA063445R1 |
Specifications may be subject to change without notice