Product Model
T6L 800 Ekip M-LRIU In=630 3p F F

Selling Points
- 1Designed for long-lasting performance with a mechanical durability of 20,000 cycles.
- 2Equipped with Ekip M-LRIU release for enhanced short-circuit performance.
- 3Constructed with double insulation and oversized insulation for safety and reliability.
- 4Suitable for use up to 690 V AC and 500 V DC, making it versatile for various electrical applications.
- 5Meets IEC 60947-4-1 standards for electrical safety and performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 210 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 9.5 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3 |
Power Loss | at Rated Operating Conditions per Pole 32 W | Rated Current (In) | 630 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (380 V AC) 75 kA (400 V AC) 75 kA (415 V AC) 75 kA (440 V AC) 60 kA (500 V AC) 49 kA (690 V AC) 22.5 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 80 kA (500 V AC) 65 kA (690 V AC) 30 kA |
Rated Uninterrupted Current (Iu) | 800 A | Release | Ekip M-LRIU |
Release Type | EL | Short-Circuit Performance Level | L |
Standards | IEC | Sub-type | T6 |
Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | UNSPSC | 39121100 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA060314R1 |
Specifications may be subject to change without notice