Product Model
T6N 630 TMA 630-6300 4p F F InN=100%In

Selling Points
- 1High Current Rating: Supports up to 630 A for reliable operation.
- 2Thermomagnetic Release: Ensures safe and efficient short-circuit protection.
- 3Front Terminal Connection: Easy installation with front terminals.
- 4IEC Compliant: Meets international standards for safety and performance.
- 5Long Durability: Withstands 7000 cycles at 60 cycles per hour for extended service life.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 280 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 12 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
Power Loss | at Rated Operating Conditions per Pole 30.6 W | Rated Current (In) | 630 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 15 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 7.6 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 25 kA (750 V DC) 3 Poles in Series 16 kA |
Rated Uninterrupted Current (Iu) | 630 A | Release | TMA |
Release Type | TM | Short-Circuit Performance Level | N |
Standards | IEC | Sub-type | T6 |
Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | UNSPSC | 39121100 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA060210R1 |
Specifications may be subject to change without notice